423
The Universal Reset Module 423 is designed to operate all of the mechanical equipment in a hydronic heating system, except for zones, coordinating their operation through network communication. It can be used in applications ranging from a single zone of baseboard with an on/off boiler, to four temperature systems comprised of multiple fan coils, baseboard, mixed radiant floor zones, and two modulating/condensing boilers. This control regulates up to four space heating water temperatures through Outdoor Temperature Reset and Indoor Temperature Feedback. It is capable of controlling two on/off or modulating boilers, Domestic Hot Water, setpoint loads, and can expand up to 24 zones for each space heating water temperature (96 in total).
Features
- Outdoor temperature reset, indoor temperature feedback
- Warm weather shut down, zone synchronization
- DHW post purge, DHW control
- DHW priority (optional), setpoint operation
- Expandable up to 96 zones, two on/off or two modulating boiler control
- Controls up to 4 water temperatures (with use of up to 3 mix expansion modules), automatic boiler differential
- Exercising, boiler protection
- Powered pump outputs, system setback (with optional timer)
- One touch overrides (with optional User Switch)
Specifications | |
---|---|
Agency Approvals | CSA C US, CSA/UL 61010-1, meets Class B: ICES & FCC Part 15 |
Ambient Conditions | Indoor use only, 32 to 122 degrees F (0 to 50 degrees C), RH 80 percent to 88 degrees F (31 degrees C), down to 50 percent from 104 to 122 degrees F (40 to 50 degrees C), Altitude less than 6560 feet (2000 m), Installation Category II, Pollution |
Boiler Relay | 115 V (ac) 5 A |
Combined Load | 10 A Maximum (for DHW and Primary Pump) |
Control Type | Microprocessor PID control, this is not a safety (limit) control |
Demand | 20-260 V (ac) / 0.1 VA at 24 V |
DHW - Valve Output | 24 V (ac) 8 VA Maximum |
Dimensions | 3 5/8 IN H x 5 3/8 IN W x 9/16 IN D (92 x 137 x 14 MM) |
Enclosure Material | Does Not Apply To Product |
Enclosure NEMA Rating | Does Not Apply To Product |
Hydronic - HVAC Control Type | Universal Reset Module |
Modulating Output | 0-10 V (dc) Minimum 2500 |
Power Supply | Provided by interconnected tekmarNet Zone Manager |
Pump Relay | 115 V (ac) 5 A, 1/6 hp |
Sensor | NTC thermistor, 10 k at 77 degrees F (25 degrees C plus / minus 0.2 degrees C) Beta = 3892 |
Literature
-
- Installation and Operation - 423 (Aug 2007 - Present)
- Job Record - 423 (Aug 2009 - Present)
- SB032 - Modulating Boiler Interface Revision 8
- SB054 - RF Noise Interference (May 2009 - Present)
- SB067 - Installing tN4 Reset Modules 420, 422 and 423 with Modulating Boilers (Mar 2011 - Present)
- SB089 - Installing tN4 Reset Modules 420, 422, and 423 with Modulating Boilers (Sep 2015 - Present)
- Specification Sheet - 423 (Jan 2011 - Present)
- Wiring Guide - 423 (Mar 2009 - Present)